Start-Up - Water Wizard (Optional)

Step 1 Open the Solenoid

Confirm that the manual water supply valve is
closed. Press and hold the function button for

one second. L3 (refer to Water Wizard operation in the
Reference section) will begin blinking (short on, long
off), indicating that flow test mode is active and the
supply solenoid is open.

Step 2 Set the Water Pressure

With the solenoid open, set the supply water
pressure to the correct setting from the following

tables. Use the manual supply valve to adjust the
supply pressure. A pressure gauge is provided between
the manual supply valve and the media.

WARNING!

Opening the manual supply valve will allow

water to pass to the media. Be sure the

sump is safely draining before opening the

manual supply valve.

NOTE!

The manual supply valve ships closed and
must be adjusted for proper performance.

NOTE!

The recommended water pressure is based on

media width. Refer to the table provided

for proper water pressure settings.

Housing

Size

Media Width

(inches)

Water

Pressure

12

30

20

22

43

3

4

36

60

61

32

66

72

96*

42

35

120*

61

38

180*

37

42

216*

51

DG-10

26

3

4

19

DG-20

66

74

DG-30

84*

35

Recommended Water Pressure Chart

*Multiple media sections. Values represent total media width.

Step 3 Break-in Media

Leave the supply solenoid open to saturate and break-
in the media for 20 minutes with the blower off.

Step 4 Close Solenoid

With the pressure set, press the function key for
one second to deactivate flow test mode and

allow the supply solenoid to close.

Step 5 Check Media

Start the cooling cycle and check the media after one
hour of operation. If the media is continuously dry or if
too much water is draining from the sump tank, refer to
Water Wizard troubleshooting.

NOTE!

Steps 6 through 8 are provided to adjust the minimum cooling temperature. The minimum cooling

temperature is preset to the factory recommended 75ºF. Only adjust if needed.

NOTE!

The inlet air sensor function overrides and shuts down the evaporative cooler if the outside

temperature falls below the minimum cooling temperature.

Step 6 Enter Program Mode

Press and hold the enter key for three seconds.
The display will read “Pro” when program mode

is active.

Program Display