Greenheck DG / DGX with Pilot Ignition (463555 IOM) (Pre-2008) User Manual

Page 38

Advertising
background image

38

Troubleshooting

Troubleshooting

Water Blows through Evaporative Cooler

Water supply greater than

evaporation and bleed-off rate?

Use the main supply valve to reduce the supply of water.

Air velocity greater than

specified?

Reduce the air velocity through the media.

(Reference Evaporative Cooler Start-Up Step #1)

Are the headers in place and

located near the entering side of

the media?

Replace headers and/or move the headers.
(Reference Evaporative Cooler Start-Up Step #1)

Yes

No

Yes

Yes

No

Note: At this time the evaporative cooler should be

operating without water blowing through.