Installation - roof mounted unit arrangement dbc, Step 1 install curb/equipment support(s), Step 2 install combination extension – Greenheck DG / DGX with Pilot Ignition (463555 IOM) (Pre-2008) User Manual

Page 5: Step 4 apply sealant, Step 3 install ductwork

Advertising
background image

Supply Duct with Duct
Adapter Installed

Exhaust Duct Installed

Sealant

Supply

Ductwork
by Others

Exhaust

Ductwork
by Others

Metal Cover

Equipment
Support

Roof Curb

Exhaust

Supply

1 inch Inside
Flange

Step 1 Install Curb/Equipment

Support(s)

Position curb/equipment support(s) on the roof
(reference the CAPS submittal for placement of
curb/equipment support(s) in relation to the unit).
Verify that all unit supports are level, shim if
necessary. Attach curb to roof and flash into place.
Attach the equipment support(s) to the roof, remove
metal cover, flash to wooden nailer and reinstall
cover.

Step 2 Install Combination Extension

Install combination extension over curb. Lag into
place using wood screws. Locate the extension so
the tall vented side is over the exhaust opening.

Installation - Roof Mounted Unit Arrangement DBC

Installation

Step 4 Apply Sealant

Apply an appropriate sealant around the perimeter of
the curb and duct adapter(s) to isolate fan vibration
and prevent water penetration.

5

NOTE!

The use of a duct adapter is recommended on a

downblast (DBC) arrangement to align the

ductwork with the supply unit. The duct adapter

is only a guide and is not to be used as support

for the ductwork.

Step 3 Install Ductwork

Good duct practices should be followed for all
ductwork. All ductwork should be installed in
accordance with SMACNA and AMCA guidelines,
NFPA 96 and any local codes. Reference the CAPS
submittal for ductwork size and location.

Curb and Equipment Support

Combination Extension

Ductwork

Sealing Ductwork

Advertising