Sensor reading, scaling, and override duration, Lead/lag controller technical guide – Orion System Lead Controller User Manual

Page 15

Advertising
background image

Lead/Lag Controller Technical Guide

Section 4: Confi guring Analog Inputs

15

Sensor Reading, Scaling, and Override Duration

Sensor Reading Appendix

Select from the drop down list in the

<Sensor Reading Appendix>

fi eld (Figure 13) to give the sensor reading a qualifi er.

● None: No Appendix Required

● RH%: Humidity Percentage

● %: Percentage

● °F: Fahrenheit

● °C: Celsius

● PPM: Parts per Million

● PSI: Pound per Square Inch

● “WG: Inches of Water Gauge

● “: Inches

● Ft.: Feet

● RPM: Revolutions per Minute

● VDC: Volts D.C.

● BTU: British Thermal Unit

● CFM: Cubic Feet per Minute

● Hr: Hours

● Min: Minutes

● GPM: Gallons per Minute

● kPa: Kilopascals

Sensor Scaling

Figure 13: Sensor Reading Appendix Field

Figure 14: Sensor Scaling Field

All readings are user-scalable according to the number of digits
to the right of the decimal point. See Figure 14 and values and
examples below.

●

X

1

65°F

● X 10

65.5°F

● X 100

65.54°F

● X 1000

65.543°F

Number of Readings to Average

This function has the capability of averaging up to 25 sensor readings
before it displays a new value on one of the Lead/Lag Controller
Status Screens
. Sensor values are read once per second.

Type the number of readings from this sensor you want to aver-
age in the

<Number of Readings to Average>

fi eld and press

<ENTER>

to save. See Figure 15. Valid entries are from 1-25.

If you want the input sensor to only show its most current reading,
enter

<1>

.

Figure 15: Number of Readings to Average Field

User Scaling

The User Scaling Box allows you to set a Maximum and Minimum
Reading for the specifi c 4-20 mA or 0-5 vdc sensor you are using.
This means you can display values with ± 1, ± 0.1, ± 0.1± 0.01 or
higher resolutions. Just keep in mind that the maximum value that
can be sent from the controller is ±30,000, so if you have scaled your
reading to ± 0.001, then the maximum value you can send is ± 30
with the 3 additional decimal values (30.000). See Figure 16. Type
in the values and press

<ENTER>

to save.

Figure 16: User Scaling Box

Advertising
This manual is related to the following products: