Orion System Lead Controller User Manual

Page 28

Advertising
background image

Section 7: Confi guring Analog Outputs

Lead/Lag Controller Technical Guide

28

Control Source

The Control Source Options are as follows (Figure 43):

Analog Inputs #1 - 8

Control Source, Control Setpoints, Setpoint Reset Source

Figure 43: Control Source

Control Setpoints & Reset Limits

For most applications, only the Max Setpoint and the Deadband will
be used. See Figure 44. Unless a Setpoint Reset Source is selected,
the other values in this section will be grayed-out and not used. In
this situation, the Max Setpoint will be the setpoint you are trying to
maintain. The Deadband is the range above and below the Setpoint
in which no control signal change is made.

Figure 44: Control Setpoints & Reset Limits

Setpoint Reset Source

You can confi gure a Setpoint Reset Source that will allow reset of the
Control Setpoints (Figure 45). Once a Reset Source is selected, you
will be able to confi gure both a “Max Setpoint” and a “Min Setpoint”
as well as a Max Reset value and a Min Reset value (Figure 46).
As the Reset Source value varies between the Max and Min Reset
values, the Control Setpoint will be proportionally reset between
the Max and Min Control Setpoints. At the Max Reset value, the
Control Source will be at the Max Setpoint, regardless if it is an
inverse relationship.

Figure 45: Setpoint Reset Source

Disabled Mode Offsets

The Disabled Mode Offsets (Figure 46) can be used if you are
using an Enabling Relay, an Enabling Binary Input, or a Control-
ling Schedule. Anytime this output is not enabled by the Enabling
Relay or the Enabling Binary, or is in the Unoccupied Mode (per the
Schedule), these offsets will be applied to the Max/Min Setpoints
to initiate the control operation of this analog output. These would
then act as “Night Setback” type offsets. If these offset values are
‘0’, there will be no Disabled Mode operation.

Figure 46: Disabled Mode Offsets

Advertising
This manual is related to the following products: