Programming The VCM Controller

Application Configurations

This area of the manual is designed to simplify the programming setup
process for typical AAON

®

units which have factory installed VCM

Controllers. Special applications are also included to guide the user
through the setup process for more complicated configurations. The
following configurations will step you through the Configuration Sec-
tion of this manual. Not all configuration screens are listed in this sec-
tion. This section is more of a quick setup guide for basic applications.
Please read each description under the corresponding Configuration
Screen in this manual to see if that option applies to your application.

Setpoints are not shown here since they are not necessarily configura-
tion specific, but are based more on job requirements. Read the descrip-
tions under the corresponding Setpoint Screens in this manual to under-
stand which setpoints to use and what values are appropriate to enter.

VAV Unit

If you need to setup your HVAC unit for VAV operation use the
following values:

Configuration Section

Screen #1 = “YES”

Screen #3 = “Supply Air”

Screen #4 = “No Reset”
Can be configured for Reset; see the Supply Air Setpoint Reset
section that follows, before configuring.

Screen #9 = “YES”
Only if equipped with an Outdoor Air Humidity Sensor for
Wetbulb control of Economizer.

Screen #12 = “YES”
Only if equipped with an Economizer.

Screen #13 = “YES”
Only if equipped with a proof of flow switch.

Screen #22 = “2”
Only if standard CO

2

Sensor is installed for IAQ Control.

Screen #23 = “2000”
This is the proper CO

2

Sensor scaling for the Standard CO

2

Sensor.

Screen #24 = “YES”
Only if equipped with VFD exhaust fan or Modulating Exhaust
Damper Actuator.

Screen #26 = “0” or “1”
Configure the proper Building Pressure Output signal.

Screen #28 = “YES”
Only if a Smoke Detector is connected to the VCM.

Screen #31 = “YES”
Only needed when connected to Orion VAV/Zone Controllers.

Screen #32 = “YES”
Only needed when connected to Orion VAV/Zone Controllers.

Screen #33 = “YES”
Only needed when connected to Orion VAV/Zone Controllers.

Screen #34 = “YES”
Only needed when connected to Orion VAV/Zone Controllers.

Screen #35 = “YES”
Only needed when connected to Orion VAV/Zone Controllers.

Screens #42-#61
Refer to the AAON

®

wiring diagram inside the unit before

configuring onboard and Expansion Board Relays.

CAV Unit

If you need to setup your HVAC unit for CAV operation use the
following values:

Configuration Section

Screen #1 = “NO”

Screen #2 = “NO”
Only configure as “YES” if the Supply Fan needs to be off
when no Heating, Cooling or Dehumidification demand exists.

Screen #3 = “Space Temperature”
Can be “Return Air”; for cooling only units, select “Supply
Air”.

Screen #4 = “No Reset”
Can be configured for Reset; see the Supply Air Setpoint Reset
section that follows, before configuring.

Screen #6 = “YES”
Only if the unit is equipped for Dehumidification.

Screen #7 = “YES”

Screen #8 = “YES”
Only if Dehumidification is needed during the Unoccupied
Mode.

Screen #9 = “YES”
Only if equipped with an Outdoor Air Humidity Sensor for
Wetbulb Control of Economizer.

Screen #10 = “YES”
Only if equipped with an Indoor Humidity Sensor for
Dehumidification.

Screen #12 = “YES”
Only if the unit is equipped with an Economizer.

Screen #13 = “YES”
Only if equipped with a Proof of Flow Switch.

Screen #22 = “2”
Only if standard CO‚ Sensor is installed for IAQ Control.

Screen #23 = “2000”
This is the proper CO‚ Sensor scaling for the Standard CO‚
Sensor.

Screen #24 = “YES”
Only if equipped with VFD Exhaust Fan or Modulating
Exhaust Damper Actuator.