Programming the vcm controller – Orion System VCM User Manual

Page 22

Advertising
background image

Technical Guide

Operator Interfaces

22

Configuration Screen #39

VCM Cnfg ID 59

Enable Broadcast To

Multiple Loops: NO

[0=NO 1=YES]

When “1=YES” is selected, all broadcasts that have been configured on
Configuration Screens 31 through 35 will be sent to all local loops on
the entire system, not just the local loop the VCM controller is on. This
is normally only required if you have a large HVAC unit that requires
more than the 58 VAV/Zone controllers normally allowed on the local
loop. This allows other VAV/Zone controllers connected on additional
local loops to receive the required broadcasts. This only is allowed when
you have a single VCM controller with VAV/Zone controllers on mul-
tiple loops. Other VCM or add-on devices may be connected but no
other VCM with VAV/Zone controllers can be connected on the sys-
tem.

Configuration Screen #40-43

VCM Cnfg ID 59

Cooling Stage Delays

Staging Up...: 3 Min
Staging Down : 1 Min

VCM Cnfg ID 59

Cooling Stage Delays

Min Run Time: 5 Min

Min Off Time: 3 Min

VCM Cnfg ID 59

Heating Stage Delays

Staging Up...: 3 Min

Staging Down : 1 Min

VCM Cnfg ID 59

Heating Stage Delays

Min Run Time: 2 Min
Min Off Time: 1 Min

Both the Heating Stages and the DX Cooling Stages utilize Staging Up
and Down Delay Periods between stages and Minimum Run Times
and Off Times.

Both modes have their own set of Staging and Run Delay Times. The
Heating Timer Screens look exactly the same as the Cooling Timer
Screens except they reference the Heating settings instead of the Cool-
ing settings.

See the Sequence of Operation Manual for information on how these
Delays and Run Times are used.

Description

Minimum

Default

Maximum

Cooling Stage Up

3 Min

3 Min

15 Min

Cooling Stage Down

1 Min

1 Min

15 Min

Cooling Min Run Time

5 Min

5 Min

15 Min

Cooling Min Off Time

3 Min

3 Min

15 Min

Heating Stage Up

3 Min

3 Min

15 Min

Heating Stage Down

1 Min

1 Min

15 Min

Heating Min Run Time

2 Min

2 Min

15 Min

Heating Min Off Time

1 Min

1 Min

15 Min

Configuration Screen #44-68

VCM Cnfg ID 59

Relay Configurations

Rly xx: Not Used

Press “0” To Change

Relay #1 is not configurable as it is reserved for the Supply Air Fan.
Relays #2-#21 are configurable for the following options:

Cooling Stage

Heating Stage

Warm-up Mode

Reversing Valve

Reheat

Pre-Heater

Exhaust Fan

Alarm

Override

Occupied

Economizer

Relays #2 through #21 can be individually configured. By using all (4)
of the available 4 Relay Expansion Boards and the 4 relay outputs avail-
able on the VCM controller, you have the ability to configure up to a
combined total of 20, Heating Stages, Cooling Stages, and options 3
through 11 listed above. Only the Heating and Cooling relays can be
configured with multiple outputs. If any other option is selected more
than once, it will simply activate redundant relays but no multiple stag-
ing will occur.

Programming The VCM Controller

Advertising
This manual is related to the following products: