Technical Guide

Operator Interfaces

36

Programming The VCM Controller

Status

The VCM controller status screens are accessed by pressing the “Sta-
tus” button on either the System Manager or the Modular Service Tool.
Following are the available status screens and a description of their
functions.

Status Screen 1

VCM v1.00 ID 59
Occupied Mode
Venting Mode
03/10/05 5:00 PM

Line 2

Line displays one of the following:

Unoccupied Mode

Remote FRC Occupied

Occupied Mode

Override Mode

Holiday Mode

Zone Demand!

Forced Schedule Mode

OUTPUT FORCE MODE!

SUPPLY AIR CUTOFF!

High CO2 Level Mode!

Line 3

If you selected Supply Air as the controlling sensor, this
line will display:

Supply Air Control

If you select Space Temp or Return Air Control the
display will show one of the following:

Venting Mode

Cooling Mode

Heating Mode

Dehumidify Mode

Line 4

Line displays one of the following:

MM/DD/YY HH:MM XX (XX = AM or PM)
Fan Starting Delay

xx Left in WarmUp (Number of Minutes Left)

Status Screen 2

VCM v1.00 ID 59
Cooling Enabled

Heating Enabled

Economizer Disabled

Line 2

Line displays one of the following:

Cooling Enabled

Cooling Disabled

Line 3

Line displays one of the following:

Heating Enabled

Heating Disabled

Line 4

Line displays one of the following:

Economizer Enabled

Economizer Disabled

Status Screen 3

VCM v1.00 ID 59

Enable Tmp : xx.x

°

F

Cooling Spt: xx.x

°

F

Heating Spt: xx.x

°

F

Line 2

Mode Enable Temperature

Can be the Supply Air Temperature, Return Air
Temperature, Outdoor Air Temperature or Space
Temperature depending on which one has been configured
as the Mode Enable Sensor

Line 3

Mode Cooling Setpoint

Based on the current Occupied / Unoccupied Mode of
operation.

Line 4

Mode Heating Setpoint

Based on the current Occupied/Unoccupied Mode of
operation.

Status Screen 4

VCM v1.00 ID 59

SAT/Reset Source

Cooling Spt: xx.x

°

F

Heating Spt: xx.x

°

F

Line 2

Supply Air Temperature Reset Source

Can be the Return Air Temperature, Space Temperature,
Fan VFD or Remote Reset Input depending on which one
has been installed and configured as the Supply Air
Temperature Reset Source.

Line 3

Currently Supply Air Temperature Reset for
Cooling Setpoint

Based on the Occupied Mode of operation.

Line 4

Currently Active Heating Setpoint

Based on the Occupied Mode of operation.