Programming the vcm controller, Technical guide operator interfaces 38 – Orion System VCM User Manual

Page 38

Advertising
background image

Technical Guide

Operator Interfaces

38

Programming The VCM Controller

S

S

S

S

Status Screen 9

VCM v1.00 ID 59
Economizer.: xxx%
OA Wetbulb.: xx.x

°

F

CO2 Level..: XXXXPPM

Line 2

Current Economizer Open Percentage

The Economizer is optional. This shows the Outdoor Air
Damper open percentage. If Economizer Control is not
configured it will display 0%.

Line 3

Current Wetbulb Temperature

The Outdoor Air Wetbulb Temperature is optional. To
display the Outdoor Air Wetbulb Temperature, an Outdoor
Air Temperature Sensor (or an Outdoor Air Temperature
Broadcast) and a Outdoor Air Relative Humidity Sensor
must be installed. If these conditions exist, this line will
display the calculated Outdoor Air Wetbulb Temperature. If
these conditions do not exist it will display 0°F.

Line 4

Current CO

2

Level

The CO

2

Level is optional. It requires a CO

2

Sensor be

installed and configured to display the CO

2

Level. If a CO

2

Sensor is not installed and configured, this line will display
0 PPM.

S

S

S

S

Status Screen 10

VCM v1.00 ID 59
Return Air..:xx.x

°

F

Supply Air..:xx.x

°

F

Supply Spt..:xx.x

°

F

Line 2

Current Return Air Temperature

This sensor is optional. If a Return Air Temperature Sensor
is not used it will display 0°F

Line 3

Current Supply Air Temperature

The Supply Air Temperature Sensor is always required. If a
Supply Air Temperature Sensor is not installed the VCM
controller will not operate correctly and will display 0°F.

Line 4

Current Active Supply Air Temperature Setpoint

This line displays the Active Supply Air Temperature
Setpoint.

S

S

S

S

Status Screen 11

VCM v1.00 ID 59
MODGAS Pos..: xxx%

MHGRV Pos...: xxx%

[Optional Equipment]

Line 2

Current MODGAS II Heating Output Signal

Indicates the percentage of the output signal being supplied
to the MODGAS II controller when you have one
connected to your HVAC unit.

If you do not have a MODGAS II controller connected to
your VCM controller this screen will indicate
[No MODGAS Connected]

Line 3

Current MHGRV II Reheat Valve Output Signal
Percentage

Indicates the percentage of the output signal being supplied
to the MHGRV II controller when you have one connected
to your VCM controller.

If you do not have a MHGRV II controller connected to
your VCM controller, this screen will indicate
[No MHGRV Connected]

Line 4

Optional Equipment

Indicates that these outputs are optional and therefore may

or

may not have live data to display.

Status Screen 12

VCM v1.00 ID 59
Mod Cooling: XXX%

Mod Heating: XXX%
[Optional Outputs]

Line 2

Current Modulating Cooling Output Signal Percentage

Indicates the percentage of the output signal being supplied
to a Modulating Cooling device when you have configured
this option for your HVAC unit. If reverse acting is
configured, this percentage will be reversed. See the
following examples for clarification.

Standard Operation:

0-10 VDC

0% = 0 VDC

100% = 10 VDC

2-10 VDC

0% = 2 VDC

100% = 10 VDC

1.5-5.0 VDC 0% = 1.5 VDC

100% = 5.0 VDC