Setpoint Screen #10

VCM Spts ID 59
Morning Warm Up
Target Temp: 70

°

F

Max Length..: 60 Min

When the VCM is configured for VAV operation and the controller en-
ters the Occupied Mode, the VCM looks at the Return Air Temperature
to determine if the unit should initiate Morning Warm-up Mode. If the
Return Air Temperature is below the Morning Warm-up Target Tem-
perature and the Max Length is greater than “0”, the VCM controller
will initiate Heating. This is considered Morning Warm-up and will
run until the Return Air Temperature rises above the Morning Warm-up
Target Temperature or the Max Length Setpoint time expires.

Description

Minimum

Default

Maximum

Morning Warm Up

Target Temp

50

°

F

72

°

F

90

°

F

Morning Warm Up

Max Length

0 Min

60 Min

240 Min

Setpoint Screen #11

VCM Spts ID 59
Dehumidification Spt

Indoor RH..: 55%
OA Dewpoint: 55

°

F

On VAV or CAV configured units that are not using 100% Outdoor Air,
when the Indoor Relative Humidity percentage rises above the Indoor
RH Setpoint the unit will start operating in Dehumidification Mode.

On MUA configured units that are using 100% Outdoor Air, when the
Outdoor Air Dewpoint Temperature rises above the OA Dewpoint
Setpoint the unit will start operating in Dehumidification Mode.

Description

Minimum

Default

Maximum

Dehumidification Spt

Indoor RH

1

%

50

%

100

%

Dehumidification Spt

OA Dewpoint

35

°

F

55

°

F

80

°

F

Programming The VCM Controller

Setpoint Screen #12

VCM Spts ID 59

Dehumidification

Coil Temperature

Setpoint: 45

°

F

During the Dehumidification Mode, the VCM uses the calculated Coil
Temperature to activate DX Cooling based on this Dehumidifcation
Coil Temperature Setpoint. The VCM uses a Suction Pressure Trans-
ducer to read Suction Pressure (the Saturation Vapor Pressure of the
Refrigerant) and converts this Suction Pressure reading to a Coil Tem-
perature value. This calculation is based on using R22 refrigerant only
and will not work with any other refrigerant. This setpoint determines

Description

Minimum

Default

Maximum

Dehumidification Coil

Temperature Setpoint

35

°

F

45

°

F

70

°

F

Setpoint Screen #13

VCM Spts ID 59

Economizer Setpoints

OAT/WB Enable: 50

°

F

If an Outdoor Air Humidity Sensor is not connected to the VCM and
the Outdoor Air Temperature falls below this Setpoint, the Economizer
can be used for Free Cooling. If an Outdoor Air Humidity Sensor is
connected to the VCM, then a Wetbulb Temperature will be calculated
and used instead of the Outdoor Air Drybulb Temperature to determine
when Free Cooling can be used.

Description

Minimum

Default

Maximum

Economizer Setpoints

OAT/WB Enable

0

°

F

55

°

F

80

°

F