Orion System VCM User Manual

Page 25

Advertising
background image

Operator Interfaces

Technical Guide

25

Setpoint Screen #8

VCM Spts ID 59

Cutoff Temperature

Lo SAT: 40

°

F

Hi SAT: 150

°

F

The VCM controller will temporarily disable Heating or Cooling if while
in Heating or Cooling Mode the Supply Air Temperature rises above
the Hi SAT Cutoff Temperature Setpoint or falls below the Lo SAT
Cutoff Temperature Setpoint. See the VCM Controller Technical Guide
for detailed information on the Lo and Hi Supply Air Temperature
Cutoff sequence of operation.

Description

Minimum

Default

Maximum

Lo SAT Cutoff

0

°

F

40

°

F

250

°

F

Hi SAT Cutoff

0

°

F

170

°

F

250

°

F

Setpoint Screen #9

VCM Spts ID 5

Minimum Supply

Fan VFD Speed

For Heating: 50%

If the Supply Fan VFD Signal falls below the Minimum Supply Fan
VFD Speed For Heating Setpoint, Heating will be disabled.

Description

Minimum

Default

Maximum

Min Supply Fan VFD

Speed For Heating

0

%

50%

100%

Setpoint Screen #6

VCM Spts ID 59

Stage Control Window

Cooling...: 5

°

F

Heating...: 5

°

F

When the VCM controller is in Cooling Mode, if the Supply Air Tem-
perature drops below the Active Supply Air Temperature Setpoint mi-
nus the Cooling Stage Control Window value, a Cooling Stage will be
deactivated after its Minimum Run Time. In the Heating Mode, if the
Supply Air Temperature rises above the Active Supply Air Tempera-
ture Setpoint plus the Heating Stage Control Window value, a Heating
stage will be deactivated after its Minimum Run Time.

Description

Minimum

Default

Maximum

Stage Control Window

Cooling

1

°

F

5

°

F

20

°

F

Stage Control Window

Heating

1

°

F

5

°

F

20

°

F

Setpoint Screen #7

VCM Spts ID 59

Outdoor Air Lockouts

Cooling...: 50

°

F

Heating...: 75

°

F

The VCM will Lockout Mechanical Heating or Cooling when the Out-
door Air Temperature is above or below these Setpoints.

Description

Minimum

Default

Maximum

Outdoor Air Lockouts

Cooling

0

°

F

50

°

F

80

°

F

Outdoor Air Lockout

Heating

50

°

F

70

°

F

90

°

F