Operator interfaces technical guide 21 – Orion System VCM User Manual

Page 21

Advertising
background image

Operator Interfaces

Technical Guide

21

Configuration Screen #31

VCM Cnfg ID 59

Broadcast Outdoor

Temperature: NO

[0=NO 1=YES]

The VCM can broadcast its Outdoor Air temperature Reading to other
HVAC units if they are not equipped with their own Outdoor Air Tem-
perature sensors. A network communications device is needed in order
for this feature to operate.

Configuration Screen #32

VCM Cnfg ID 59

Broadcast Outdoor

Humidity: NO

[0=NO 1=YES]

The VCM can broadcast its Outdoor Air Humidity reading to other
HVAC units if they are not equipped with their own Outdoor Air Hu-
midity sensors. A network communications device is required in order
for this feature to operate.

Configuration Screen #33

VCM Cnfg ID 59

Broadcast Supply

Temperature: YES

[0=NO 1=YES]

This broadcast sends the VCM’s Supply Air Temperature to all con-
trollers on its local loop. This broadcast needs to be configured on a
VAV or Zoning System using the VCM with Orion VAV/Zone Control-
lers. A network communications device is required in order for this
feature to operate.

Configuration Screen #34

VCM Cnfg ID 59

Broadcast Status

Fan & Heat: NO

[0=NO 1=YES]

This broadcast sends the VCM’s Supply Fan and Heating Status to all
controllers on its local loop. This broadcast needs to be configured on a
VAV or Zoning System using the VCM with Orion VAV/Zone Control-
lers. A network communications device is required in order for this
feature to operate.

Configuration Screen #35

VCM Cnfg ID 59

Broadcast Internal

Time Clock: NO

[0=NO 1=YES]

This broadcast sends the time from the VCM’s Internal Time Clock to
all controllers on its local loop. This broadcast needs to be configured
on a VAV or Zoning System using the VCM with Orion VAV/Zone
Controllers. A network communications device is required in order for
this feature to operate, but can also be used to synchronize all control-
lers on the local loop.

Configuration Screen #36

VCM Cnfg ID 59

Broadcast Internal

Schedule: NO
[0=NO 1=YES]

This is always required when you have VAV/Zone controllers connected
to this VCM controller. This will broadcast the Occupied and Unoccu-
pied Condition of the VCM controller to all VAV/Zone controllers on
the local loop.

Configuration Screen #37

VCM Cnfg ID 59

Broadcast VAV Boxes

Force To Max : NO

[0=NO 1=YES]

This broadcast is to ensure the VAV/Zone Controllers will drive their
dampers to the Max Airflow Damper Position during Morning Warm-
up. This is important to allow the proper amount of airflow for Heating
in the HVAC unit.

Configuration Screen #38

VCM Cnfg ID 59

Broadcast VAV Boxes

Force To Fixed : NO

[0=NO 1=YES]

When “1=YES” is selected all VAV/Zone controllers connected to this
VCM controller will be Forced to their “Fixed Airflow” Position dur-
ing the Morning Warmup Mode of operation. Select “0=NO” if you do
not want this to occur. See the VAV/Zone controller Setpoint Screens
for setting of the “Fixed Airflow” Position.

Advertising
This manual is related to the following products: