Operator interfaces technical guide 27 – Orion System VCM User Manual

Page 27

Advertising
background image

Operator Interfaces

Technical Guide

27

Setpoint Screen #16

VCM Spts ID 59

CO2 Protection Limit

Max Level..: 900 PPM

Reset Rnge.: 100 PPM

When the CO

2

level rises above the CO

2

Protection Limit Max Level,

the Economizer’s Minimum Position will begin to reset open propor-
tionally between the CO

2

Protection Limit Max Level Setpoint and the

Reset Range Setpoint. The Reset Range value is added to the Max Level
value. If the CO

2

levels are equal to or above the Max Level plus the

Reset Range, the Economizer will be opened to its Maximum Econo-
mizer Position if high CO

2

levels occur.

Description

Minimum

Default

Maximum

CO2 Protection Limit

Max Level

0 PPM

900 PPM

3000 PPM

CO2 Protection Limit

Reset Rnge

0 PPM

100 PPM

1500 PPM

Setpoint Screen #17

VCM Spts ID 59

Static Spt...: 0.50”

Deadband.....: 0.10”

Control Rate.: 10 s

For VAV units, a Supply Fan VFD or a Bypass Damper Actuator is
used to maintain the Duct Static Pressure Setpoint. The Static Pressure
Output Signal varies to control the Static Pressure Setpoint. If the Duct
Static Pressure is above the Static Setpoint plus the Deadband, the Static
Pressure Output Signal will be reduced at every Control Rate interval.
If the Static Pressure is below the Static Setpoint minus the Deadband,
the Output signal will be increased at every Control Rate interval.

The Duct Static Pressure Control Output Signal is a non-configurable
Direct Acting Signal (0-10 VDC). This can be used to directly connect
to a Supply Fan VFD without any modifications.

When you are using a Bypass Damper Actuator to control the Duct
Static Pressure, you must set up the Bypass Damper Actuator or the
Bypass Damper so that it is Reverse Acting in operation. The Output
Signal increases (closes Bypass Damper) if the Duct Static Pressure is
below the Duct Static Pressure Setpoint by the Deadband amount and
the Output Signal decreases (opens Bypass Damper) if the Static Pres-
sure is above the Setpoint by the Deadband amount.

Description

Minimum

Default

Maximum

Static Spt

0.10” WG

0.50” WG

3. 0” WG

Deadband

0.01” WG

0.10” WG

1.0” WG

Control Rate

1 Sec

10 Sec

30 Sec

Setpoint Screen #14

VCM Spts ID 59

Economizer Setpoints

Min Position.: 10%

Control Rate: 90

The Economizer (Outdoor Air Damper) Min Position Setpoint is main-
tained during the Occupied Mode even if the Economizer is disabled
due to the Outdoor Air Temperature or Wetbulb Temperature being above
the Economizer Enable Setpoint. The Control Rate Setpoint allows the
user to adjust the Economizer to modulate the Outdoor Air Damper
Actuator faster or slower as desired. The Control Rate Setpoint range is
1-99. Larger numbers make the Economizer Outdoor Air Damper
Actuator modulate faster, smaller numbers make the Outdoor Air Damper
Actuator modulate slower.

Description

Minimum

Default

Maximum

Economizer Setpoints

Min Position

0

%

10

%

100

%

Economizer Setpoints

Control Rate

10

90

99

Setpoint Screen #15

VCM Spts ID 59

Maximum Economizer

Position If High CO2

Level Occurs: 100%

This Setpoint allows the user to set the Maximum Position the Econo-
mizer will open if high CO

2

conditions occur in the space. The Maxi-

mum Economizer Position Setpoint is used to limit the amount of Out-
door Air that will be introduced to the HVAC unit in order to ensure the
unit is operating within its Heating and Cooling design limitations. As
shown in the table below the Minimum setting for this Setpoint is the
value previously set for the Economizer Min Position Setpoint.

Description

Minimum

Default

Maximum

Maximum Economizer

Position If High CO2

Level Occurs

Economizer

Minimum

Position

100%

100%

Advertising
This manual is related to the following products: