Operator interfaces technical guide 23, Setpoints - general procedures, Setpoint screen index – Orion System VCM User Manual

Page 23

Advertising
background image

Operator Interfaces

Technical Guide

23

Setpoint Screen #13

Economizer Setpoints OAT/WB Enable

Setpoint Screen #14

Economizer Setpoints Min Position &
Control Rate

Setpoint Screen #15

Maximum Economizer Position If High
CO2 Level Occurs

Setpoint Screen #16

CO2 Protection Limit Max Level &
Reset Range

Setpoint Screen #17

Static Spt, Deadband & Control Rate

Setpoint Screen #18

Building Pressure Setpoint & Deadband

Setpoint Screen #19

Return Air Bypass Damper Factor
Setpoint

Setpoint Screen #20

Fan Starting Delay Timer

Setpoint Screen #21

Mechanical Heat Cool Failures Occur
After No Change For

Setpoint Screen #22

Low OA Ambient Protection
Temperature

Setpoint Screen #23

HVAC Schedule

Setpoint Screen #24

Push-button Override Duration

Setpoint Screen #25

HVAC Mode Sensor Slide Offset

Setpoint Screen #26

Air To Air Heat Pump Auxiliary
Heating Delay

Setpoint Screen #27

Internal Schedule Optimal Start Soak
Multiplier

Setpoint Screen #28

Sensor Calibration For SPC & SAT

Setpoint Screen #29

Sensor Calibration For RAT & OAT

Setpoint Screen #1

VCM Spts ID 59

HVAC Mode Setpoints

Cooling......: 75

°

F

Heating......: 70

°

F

These Setpoints are used to determine the Heating, Cooling or Vent
Modes of operation in reference to the HVAC Mode Enable Sensor. If
the Supply Air Sensor is configured to be the HVAC Mode Enable,
these Setpoints are used in conjunction with the Unoccupied Setbacks
if equipped with a Space Temperature Sensor.

Description

Minimum

Default

Maximum

HVAC Mode Setpoints

Cooling

0

°

F

75

°

F

90

°

F

HVAC Mode Setpoints

Heating

0

°

F

70

°

F

90

°

F

Setpoints - General Procedures

System Manager Instructions

From any menu screen press the “Setpoint” key. The unit selection screen
will appear requesting that you enter the unit ID number. Enter the cor-
rect unit ID number of the VCM controller you want to change Setpoints
for and press the “Enter” key. You will see the screen shown below.

1)Change Setpoint
2)Configure Unit

3)Damper Force

ESC) Exit Menu

Press “1” on the keypad to enter the first unit Setpoint screen.

Modular Service Tool Instructions

From any menu screen press the “Setpoint” key. The unit selection screen
will appear requesting that you enter the unit ID number. Enter the cor-
rect unit ID number of the VCM controller you want to change Setpoints
for and press the “Enter” key. You will then see Setpoint screen #1.

Setpoint Screen Index

The available Setpoint Screens for the VCM controller are listed on the
next few pages by sequential screen number. When each VCM control-
ler is configured for the first time, it is best to start with screen #1 and
proceed to each Setpoint Screen in numerical order until you have
viewed all available Setpoint Screens. This ensures that you have seen
all the available VCM controller Setpoint possibilities and have the
opportunity to change or accept the defaults for each screen. Once the
unit Setpoints are configured and you decide to change one of the screen
options it is helpful to know what screen number contains the configu-
ration you wish to change. With this in mind, following is a list of all
the VCM Setpoint Screens in numerical order with a brief listing of the
Setpoint feature available on each screen.

Setpoint Screen #1

HVAC Mode Setpoints

Setpoint Screen #2

HVAC Mode Select Deadband

Setpoint Screen #3

Unoccupied Setbacks

Setpoint Screen #4

SAT/Reset Source Setpoints

Setpoint Screen #5

Remote SAT Reset Setpoints

Setpoint Screen #6

Stage Control Window

Setpoint Screen #7

Outdoor Air Lockouts

Setpoint Screen #8

Cuttoff Temperature Lo SAT & Hi SAT

Setpoint Screen #9

Minimum Supply Fan VFD Speed For
Heating

Setpoint Screen #10

Morning Warm-up Target Temp & Max
Length

Setpoint Screen #11

Dehumidification Indoor RH & OA
Dewpoint Setpoints

Setpoint Screen #12

Dehumidification Coil Temperature

Advertising
This manual is related to the following products: