DIDCSU E1 Version

4-26

Verilink DIDCSU 2912 User Manual

Table 4-14 Net Port Alarm Threshold Configuration Menu Parameters

Command

Description

Options

Pn

Dn

Alarm Reporting: Enabling alarm reporting transmits alarm messages to

both the ASCII interface and Node Manager. If this option is set to No,

alarms will not be reported. The LEDs turn red in an alarm condition. Set

this option to No when configuring the node. Set to Yes during normal

operation.

Yes or No

(Y/N)

Fn

Loss-of-Frame (LOF) Threshold/LOF Interval: Use this option to indicate

an interval that is greater than the threshold.

Threshold:

1—86400

0 to disable

Interval:

3—86400

seconds

Ln

Loss-of-Signal (LOS) Threshold/LOS Interval: Use this option to indicate an

interval that is greater than the threshold.

If LOS occurs, troubleshoot this situation first and ignore all other

alarms. (There will be other alarms.) This is the most severe alarm.

Threshold:

1—86400

0 to disable

Interval:

3—86400

seconds

Rn

Remote Alarm Indication (RAI) Threshold/RAI Interval: Use this option to

indicate an interval that is greater than the threshold.

Threshold:

1—86400

0 to disable

Interval:

1—86400

seconds

An

Alarm Indication Signal (AIS) Threshold/AIS Interval: Use this option to

indicate an interval that is greater than the threshold.

Threshold:

1—86400

0 to disable

Interval:

1—86400

seconds

Bn

Bipolar Violation (BPV) Threshold/BPV Interval: Use this option to indicate

an interval that is greater than the threshold.

Threshold:

1—86400

0 to disable

Interval:

1—86400

seconds

En

Errored Seconds (ES) 15 min. Threshold/ES 24 hr. Threshold: An ES alarm

indicates a second with one or more errors.

15 minute

Threshold:

1—900

0 to disable

24 hour

Threshold:

1—86400

0 to disable