Switching inputs and outputs x41 (ext), Option with nd 920/nd 960) pin layout, Switching inputs and outputs – HEIDENHAIN ND 920 User Manual

Page 61

Advertising
background image

61

Signal level

Low

High

Inputs

–0.5 V

U

0.9 V I

6 mA

3.9 V

U

15 V

Pins 2, 3, 4

Switching Inputs and Outputs X41 (EXT)

(Option with ND 920/ND 960)

Pin layout

Pin

Function

10

0V for switching ranges

23, 24, 25

+24 Vdc for switching ranges

11

ND ready for operation

14

Display value outside switching range 0

15

Display value outside switching range 1

16

Display value outside switching range 2

17

Display value outside switching range 3

18

Display value outside switching range 4

19

Display value outside switching range 5

20

Display value outside switching range 6

21

Display value outside switching range 7

1

0 V (internal)

2

Reset X axis display to zero

3

Reset Y axis display to zero

4

Reset Z axis display to zero (ND960 only)

8

Pulse: output measured value

9

Contact: output measured value

5, 6, 7, 12,

Do not assign

13, 22

Inputs

Outputs

Switching Inputs and Outputs

The outputs at connection X41 are metalically isolated
from the device electronics by means of optocouplers.

Danger for internal components!
Voltage sources for external circuitry must conform
to the recommendations in EN 50 178 for
low-voltage electrical separation.

Connect inductive loads only with a quenching
diode parallel to the inductance.

Use only shielded cable!
Connect the shield to the connector housing.

Interface X41 complies with the recommendations
in EN 50 178 for separation from line power.

Advertising