ExtVfOk

External voltage and
frequency OK

External voltage and frequency are within the valid
range for connection.

GdOn

Utility grid

Relay switching when utility grid is available and
connected.

Error

Error

Sunny Island has a fault; in case of fault, contact is
open (relay is deactivated).
If the autostart is activated, the error status will be
left within 15 s and restart triggered. If the start is
unsuccessful this procedure will be repeated until
the autostart counter has expired.

Warn

Warning

The Sunny Island has warning pending. If the
warning disappears, the "Warning" state is quit.
When a warning disappears depends on the type
of warning.

Run

Run

Sunny Island is in operation, contact is closed
(relay is activated) if the device is running in
inverter operation.

BatFan

Battery Fan

Relay is used for automatic battery room ventilation
(switching the fan).
The "BatFan" function is responsible for the
ventilation of the battery room and provides
ventilation of the room in the event of battery
gassing.

AcdCir

Acid Circulation

Relay is used for automatic acid circulation
(switching the electrolyte pump)
The acid circulation enables mixing of the acid and
thus reduces acid stratification in the battery.

MccBatFan

Multicluster battery fan

Relay is used for automatic battery room ventilation
(switching the fan).
"MccBatFan" is the request from the master of the
main cluster that is transmitted to a master of an
extension cluster in order to use its relay for the
battery room ventilation.

Function/
Setting

Meaning

Function description