3 external settings (230#) – SMA SI 4548-US User Manual

Page 170

Advertising
background image

19  Parameter Lists

SMA America, LLC

170

SI4548-6048-US-BE-en-20

Operating Manual

226# BMS Mode Basic / Off

-

19.2.3 External Settings (230#)

231# Ext General

03

BatCurGain50

External battery current
sensor type (50 mV
type)

0 A to
1,000 A

100 A/
50 mV

04

BatCurAutoCal

Automatic calibration
of external battery
current sensor

Start

Start automatic
calibration

No. Name

Description

Value

Explanation

Default
value

01

BatChrgVtgMan Manual setpoint of the

battery charging
voltage with disabled
battery management
in V

41.0 V to 63.0 V

54.0 V

02

BatDiChgVtg

Minimum charging
voltage of the battery

42 V to
BatDiChgVtgStr

44 V

03

BatDiChgVtgStr Start voltage after

undervoltage detection

BatDiChgVtg to
BatChrgVtgMan

48 V

04

BatRes

Internal resistance of
the battery

0 mOhm to
200 mOhm

0 mOhm

No. Name

Description

Value

Explanation

Default
value

01

PvFeedTmStr

Start feed-in operation

04:00:00

02

PvFeedTmStp

Stop feed-in operation

22:00:00

03

ExtLkTm

Lock time after reverse
power or relay
protection

0 min to 60 min

20 min

No. Name

Description

Value

Explanation

Default
value

Advertising