19  Parameter Lists

Operating Manual

SI4548-6048-US-BE-en-20

171

232# Grid Control

05

ExtSrc

generator and grid
operating mode

PvOnly

PV only

PvOnly

Gen

Generator

Grid

Utility grid

GenGrid

Generator/
utility grid

12

ChpEna

Combined heat and
power plant

Disable

Deactivated

Disable

Enable

Activated

No. Name

Description

Value

Explanation

Default
value

01

GdVtgMin

Minimum grid voltage

105.6 V

02

GdVtgMax

Maximum grid voltage

132 V

03

GdCurNom

Nominal grid current

30 A

04

GdFrqNom

Nominal grid
frequency

60 Hz

05

GdFrqMin

Minimum power
frequency

59.3 Hz

06

GdFrqMax

Maximum power
frequency

60.5 Hz

07

GdVldTm

Minimum time required
for grid (voltage and
frequency) to be within
permissible range for
connection

300 sec

08

GdMod

Grid interface

GridCharge

Charging on the
utility grid

GdFeed

GridFeed

Charge and
feedback on the
utility grid

09

GdRvPwr

Permissible grid reverse
power (active power)

0 W to 5,000 W

100 W

10

GdRvTm

Permissible time for
grid reverse power

0 sec to 60 sec

5 sec

No. Name

Description

Value

Explanation

Default
value