11  Data Storage on SD Memory Card

Operating Manual

SI4548-6048-US-BE-en-20

99

Proceed as follows for a firmware update:

1. Create a backup copy of the existing parameter lists (see Section 11.3 "Saving and Loading

Parameters", page 97).

2. Download the latest firmware version from the Internet at www.SMA-America.com.
3. Copy the "UPDATE.BIN" file to the SD memory card.
4. Set the master device to standby.
5. Insert the SD memory card into the slot of the master.

☑ The update will be performed.

6. Press and hold <ENTER>.

☑ The Sunny Island starts. The update has been completed.

Firmware Update in a System with One Sunny Island

During the update, the Sunny Island displays the following
messages.

Observe the following:

• You may only download firmware versions from www.SMA-America.com. Using

unauthorized firmware versions cancels the warranty.

• None of the already existing parameter settings are changed or erased during a firmware

update.

• New parameters are assumed with default values.
• If there is an update to the firmware version greater or equal to 6.000, the battery

management is automatically reset. All set parameters are lost.

• Do not activate the DC circuit breaker during the firmware update.
• Do not switch off the Sunny Island during the firmware update.

Reset after a successful update
After the update has been successfully completed a reset is enforced in order for the changes
to become effective. After the reset, the master device remains in standby mode.

Starting QCG
If you have carried out a firmware update in which the number before the dot in the firmware
version has changed, it is advisable to start QCG and to perform all settings anew.