19  Parameter Lists

Operating Manual

SI4548-6048-US-BE-en-20

175

04

GnSocTm1Stp

SOC limit for switching
off generator for time 1

80%

05

GnSocTm2Str

SOC limit for switching
on generator for time 2

40%

06

GnSocTm2Stp

SOC limit for switching
off generator for time 2

80%

07

GnTm1Str

Time 1 for generator
request in hours,
minutes and seconds
Start: time 1, end: time
2

08

GnTm2Str

Time 2 for generator
request in hours,
minutes and seconds
Start: time 2, end: time
1

09

GnPwrEna

Generator request
based on power

Off

Disable

Off

On

Enable

10

GnPwrStr

Generator request,
connection power limit

4 kW

11

GnPwrStp

Generator request,
disconnection power
limit

2 kW

12

GnPwrAvgTm

Average time for
power-related
generator start

60 sec

13

GnTmOpEna

Time-controlled
generator operation

Disable

Disable

Disable

Enable

Enable

14

GnTmOpStrDt

Starting date for
time-controlled
generator operation

2010-01-
01

15

GnTmOpStrTm

Starting time for
time-controlled
generator operation in
hours, minutes and
seconds