6  Electrical Connection

SMA America, LLC

60

SI4548-6048-US-BE-en-20

Operating Manual

Generator start

The Sunny Island can control generators. The Sunny Island directly supports generators that can be
started/stopped using a single contact.

6.4.7 BatVtgOut Power Supply

The battery voltage is conducted to the outside at these terminals. The battery voltage is fused at both
poles by PTC resistors (max. 0.75 A). Depending on the internal temperature of the Sunny Island, the
tripping threshold is over 0.75 A.
This connection can be used, for example, to supply a DC contactor for load shedding.

Connecting the BatVtgOut Voltage Supply

1. Pierce a hole at a suitable location in the cable support sleeve using a sharp object.
2. Starting from the outside, lead the insulated conductors with bootlace ferrules through the hole

in the Sunny Island.

Default settings of the relays
Relay 1 is preset to the "AutoGn" generator start function and relay 2 to the "AutoLodSoc" load
shedding function.