SMA SI 4548-US User Manual

Page 172

Advertising
background image

19  Parameter Lists

SMA America, LLC

172

SI4548-6048-US-BE-en-20

Operating Manual

233# Grid Start

15

GdAlSns

AI sensitivity

Low

Low

Normal

Medium

Medium

Normal

Normal

High

High

37

GdVtgIncProEna Voltage increase

protection

Disable

Disable

Disable

Enable

Enable

38

GdVtgIncPro

Limit for voltage
increase protection

132 V

41

GdSocEna

Activate the grid
request based on SOC

Disable

Disable

Disable

Enable

Enable

42

GdPwrEna

Activate the grid
request based on
power

Disable

Disable

Disable

Enable

Enable

No. Name

Description

Value

Explanation

Default
value

01

GdSocTm1Str

SOC limit for switching
on utility grid for time 1

40%

02

GdSocTm1Stp

SOC limit for switching
off the utility grid for time
1

80%

03

GdSocTm2Str

SOC limit for switching
on utility grid for time 2

40%

04

GdSocTm2Stp

SOC limit for switching
off the utility grid for time
2

80%

05

GdTm1Str

Time 1 for grid request in
hours, minutes and
seconds
Start: time 1, end: time 2

06

GdTm2Str

Time 2 for grid request in
hours, minutes and
seconds
Start: time 2, end: time 1

No. Name

Description

Value

Explanation

Default
value

Advertising