20  Troubleshooting

Operating Manual

SI4548-6048-US-BE-en-20

223

2. Confirm the following view with <ENTER>.

3. Set the maximum external current, e.g. that of the

generator.

4. Confirm the set value with <ENTER>.

5. Use the down arrow key.

☑ The display on the right appears.

6. Press <ENTER> to confirm.

7. Press <ENTER>.

☑ The emergency charge mode is started.

Interrupt the emergency charge mode, e.g. in order to refill diesel:

1. Press <ENTER> to stop the Sunny Island.

☑ The notification shown here is displayed.

2. Press and hold <ENTER>.

☑ The remaining time is displayed as a bar.

☑ The emergency charging mode is interrupted. The

notification shown here is displayed.

Prematurely ending the Emergency Charge Mode
In order to exit the emergency charge mode early, the Sunny Island must be restarted with
parameter "510.01 InvRs".