3 switching a multicluster system on and off, 1 switching on/starting, 2 stopping and switching off – SMA SI 4548-US User Manual

Page 145: 3 load shedding in a multicluster system

Advertising
background image

SMA America, LLC

16  Multicluster Operation

Operating Manual

SI4548-6048-US-BE-en-20

145

16.3 Switching a Multicluster System On and Off

16.3.1 Switching On/Starting

Switching on a Multicluster system can only take place at the master of the main cluster. The extension
clusters will be started automatically after starting the main cluster. To do this, the DC circuit breakers
of all Sunny Island inverters in the extension cluster must be set to "ON".
Proceed as follows:

1. Perform steps 1 to 4 of the start-up procedure on the master of the main cluster (see Section 9.1

"Switching On", page 74).

☑ The masters of the extension clusters show the

following message:

2. Press and hold <ENTER> on the main cluster

master.

☑ The remaining time is displayed as a bar.

☑ An acoustic signal sounds. The main master is on

and in operation. The green LED is glowing.

16.3.2 Stopping and Switching Off

The Sunny Island Multicluster system can only be stopped at the master of the main cluster. Proceed
at the master of the main cluster as described in Sections (see Section 9.2 "Stopping the Sunny Island
(Standby)", page 75) and (see Section 9.3 "Switching Off", page 75).

16.3.3 Load Shedding in a Multicluster System

The load-shedding contactor in the Multicluster Box is controlled depending on the state of charge of
the batteries.

Starting the Multicluster system
The Multicluster system is started once the main master has started. All extension clusters follow
the main master.

Error occurrence
If the Sunny Island displays an error message, this must be remedied before the Sunny Island is
commissioned (see Section 20 "Troubleshooting", page 203).

Advertising
This manual is related to the following products: