background image

5.2 Message Send Function

5.2.4 Parameter List for MSG-SND Function

5-10

5.2.4 Parameter List for MSG-SND Function

The Param input to the MSG-SND function is a parameter list structure consisting of 17 words. The value of the Param
input is the leading address (MA or DA) of the parameter list.
Use the parameter list to input the connection number, function code, and other related parameters. The processing
results and status are also output to the parameter list.
The following table shows the parameters to be used when MEMOBUS is used as the transmission protocol for Ether-
Net/IP.

Œ

IN: Input, OUT: Output, SYS: Used by the system.

Œ

Refer to 5.2.5 Details of Parameters Used in Explicit Message on page 5-11 for details on the parameters.

Param No.

IN/OUT

Contents

Description

00

OUT

Processing result

The processing results are output here.

01

OUT

Status

The status of the current MSG-SND function is output here.

02

IN

Remote connection number The connection number of the remote station is set.

03

IN

Option Not

used

04

IN

Function code

For explicit message communication, set 03H.

Œ

Usually, function code 03H is used to read the contents of
holding registers. With explicit messages, however, it does
not have that function.

05

IN

Data address

PARAM05 sets the leading address of the M registers used in
explicit message communication within the range of 0 to 65535.

06

IN

Data size

Data size is set within the range of 1 to 504 bytes.

07

IN

Remote CPU number

Not used

08

IN

Coil offset

Not used

09

IN

Input relay offset

Not used

10

IN

Input register offset

Not used

11

IN

Holding register offset

Not used

12 to 16

SYS

Reserved by the system