DeviceNet Polled I/O Messaging Communications

DeviceNet Communications between a Master (PLC or PC) and the drive (Slave) uses Polled I/O messaging, based from the
following I/O Assemblies, to transfer control and diagnostic information to and from the drive. The “Input Data Assemblies”
or “Polled Consuming Assemblies (PCA)” refer to a message sent from the Master to the drive. The “Output Data
Assemblies” or “Polled Producing Assemblies (PPA)” refer to the response from the drive back to the Master. The factory
default of the drive DeviceNet is Extended Speed Control Input Instance 21 and Extended Speed Control Output Instance 71.

The configuration software uses the EDS file to change the PCA and PPA. By accessing the EDS file through configuration
software, the PCA and PPA can be accessed under the DeviceNet Parameter Groups “Polled Consuming Assembly” and
“Polled Producing Assembly”. Set the appropriate value using the table below and save the changes to the device.

Be sure to power down the drive, then power up to store the changes made to the PCA and PPA.

The tables in the following pages indicate the format and structure of the I/O Assemblies.

Note:

1. Regardless if I/O Data Exchange is enabled or disabled, communications will occur at the determined intervals

set by the Master.

2. Input Data Assemblies = Polled Consuming Assemblies

Output Data Assemblies = Polled Producing Assemblies

Table 12: Supported Service

Service Code

(Hex)

Service Name

Description of Service

0E

Get_Attribute_Single

Designated attribute content is read.

10

Set_Attribute_Single

Designated attribute content is changed.

Class

Instance

Attribute

Type

Data

Description

101

(65 Hex)

1

1

PPA

(Output Data

Assembly)

70

(46 Hex)

Basic Speed Control Output Instance 70

71

(47 Hex)

Extended Speed Control Output Instance 71

*default

150

(96 Hex)

Drive Modbus I/O Control Output Instance 150

151

(97 Hex)

Drive Standard Drive Control Output Instance 151

2

PCA

(Input Data

Assembly)

20

(14 Hex)

Basic Speed Control Input Instance 20

21

(15 Hex)

Extended Speed Control Input Instance 21

*default

100

(64 Hex)

Drive Modbus I/O Control Input Instance 100

101

(65 Hex)

Drive Standard Drive Control Input Instance 101