Basic speed control input instance 20 (14 hex) – Yaskawa DeviceNet Option Card CM059 User Manual

Page 35

Advertising
background image

35

Basic Speed Control Input Instance 20 (14 Hex)

This function is the basic I/O instance of Assembly Object Class (04 Hex) Attribute (03 Hex), which defines DeviceNet AC
Drive Profile. Both input/output use 4 bytes each.

Table 13: Drive Basic Speed Control Instance 20 (14 Hex) (INPUT ASSEMBLY)

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Fault Reset

Fwd Run

1

2

Speed Reference (Lower Byte)

3

Speed Reference (Upper Byte)

Data

Name

Description

Byte 0, Bit 0

Run Fwd

The drive runs forward

0: Stop
1: FWD run

Byte 0, Bit 2

Fault Reset

The drive from fault detection status is reset.

0: Fault reset off
1: Fault reset

Byte 2, 3

Speed Reference

The drive speed reference is set.
Speed command data:

Frequency reference [RPM]×1/2

SS

where

SS

: Speed Scale

*1

Setting range:

0xFFFF Hex

*2

Example: When setting 1800r/min reference, (Speed scale = 0)

Speed reference data: 1800 X 1/2

0

= 0708 Hex

Lower Byte (byte 2) = 08 Hex, Upper Byte (byte 3) = 07 Hex

Notes: *1 Speed scale can be set by explicit messaging communication AC/DC Drive Object (Class 2A Hex) attribute 16.

*2 Setting of a speed exceeding the drive maximum output frequency (E1-04) will be limited by the maximum output frequency (E1-04).
*3 When applying a speed reference make sure to set No. of poles (2 ~ 39) to the drive parameter o1-03 (frequency reference set/display unit

selection).