Fault Diagnostics

The following is a table of faults caused by the option that will be displayed on the Digital Operator, their causes, and possible

solutions. For any fault displayed on the operator that is not listed in the following table, please see the drive Users Manual.

Table 45: Drive Faults Caused by the Option

Fault

Display

Content

Cause

Solution

BUS

Option

Communication error

Communication is not
established between
DeviceNet master and the
drive.

Check DeviceNet communication LED display
and connection at DeviceNet terminal.
The network and/or 24VDC power supply may be
down.

EF0

External Fault from

Option

External fault is active from
DeviceNet option.

Turn OFF external fault input.

CPF06

Option Connection

Fault

The drive and communication
are not correctly connected.

Turn OFF the drive power supply. Check the
connection of the option and drive, and then, turn
ON the drive power supply. If the fault persists,
change the option.

CPF21

Communication

Option Self-diagnostic

Fault

Communication option is not
working.

Turn the drive power supply back ON. If the fault
persists, change the option.

CPF22

Communication

Option Model Code

No. Fault

CPF23

Communication

Option Mutual

Diagnostic Fault

Advertising