Fig. 9 maximum cable distance – Yaskawa DeviceNet Option Card CM059 User Manual

Page 68

Advertising
background image

68

Dropline length is the longest cable distance measured from the tap on the trunkline to each of the transceivers of the nodes on

the dropline. The total amount of dropline allowable on the network depends upon the data rate. Refer to the following dropline

budget when determining the number and length of droplines.

Baud Rate

Drop Length

Maximum

Cumulative

125 kbaud

6 meters (20 ft)

156 meters (512 feet)

250 kbaud

78 meters (256 feet)

500 kbaud

39 meters (128 feet)

0

20

40

60

80

10

0

100 200 300 400 500

125

kbaud

250

kbaud

500

kbaud

Length of
Thin Cable
(meters)

Length of Thick Cable (meters)

At 125 kbaud: L

thick

+ (5.0 x L

thin

) = 500

At 250 kbaud: L

thick

+ (2.5 x L

thin

) = 250

At 500 kbaud: L

thick

+

L

thin

=

100

(where L

thick

is the length of thick cable and

L

thin

is the length of thin cable.)

Fig. 9 Maximum Cable Distance