Table 37: Object Content

Instance

(Hex)

Attribute

(Hex)

Name

Description

Setting

Range

Initial

Value
(Hex)

Read

Write

Size

00

01

Object Software

Revision

Control supervisor object software revision is
displayed.

0001

o

Word

01

03

Forward Run

The drive runs forward.
00: Stop
01: Forward run

00,01

00

o

o

Byte

04

Reverse Run

The drive runs reverse.
00: Stop
01: Reverse run

00,01

00

o

o

Byte

05

NetCtrl

Run command rights displayed. *1
00: Run command input method set by run

command selection (n003)

01: Run command (byte 0 – bit 0, 1) is enabled

through DeviceNet.

00,01

00

o

o

Byte

06

Inverter Status

The drive status is displayed.
03: Inverter ready

03

o

Byte

07

During

Forward Run

The drive run status is displayed.
00: During stop/reverse
01: During forward run/DC braking

00

o

Byte

08

During Reverse

Run

The drive run status is displayed.
00: During stop/forward/DC braking
01: During reverse

00

o

Byte

09

Inverter Ready

The drive operation preparing status is displayed.
00: During fault detection/preparation
01: Ready

00

o

Byte

0A

Fault

The drive fault detection status is displayed.
00: Normal
01: During fault detection

00

o

Byte

0B

Alarm

The drive alarm detection status is displayed.
00: Normal
01: During alarm detection

00

o

Byte

0C

Fault Reset

The drive is reset through fault detection status.
00: Fault reset off
01: Fault reset

00,01

00

o

o

Byte

0D

Fault Code

The drive fault detection content is displayed by the
code listed in the table below. *3

0000

o

Word

0F

Ctrl From Net

The drive run command input selection status is
displayed.*1
00: Run command input other than the DeviceNet is

enabled.

01: Run command input is enabled through

DeviceNet.

00

o

Byte

10

DeviceNet

Fault Mode

Mode selection is displayed when DeviceNet
becomes fault.*2
02: Manufacturer

02

o

Byte

11

External Fault

from Option

External fault (EF0) is input
00: EF0 Not Active
01: External fault (EF0)

00,01

00

o

o

Byte

12

External Fault

Input Status

from Option

External fault (EF0) input status is displayed.
00: EF0 Not Active
01: During external fault (EF0) input

00

o

Byte

Notes:

*1 A setting during drive operation cannot be changed.

*2 DeviceNet communication fault cannot be set. The drive detects fault and stops at DeviceNet communication fault. The drive stopping method at

communication fault can be selected by time-over detection selection parameter (n151).

*3 Fault Code (See below table for interpretation)