Yaskawa DeviceNet Option Card CM059 User Manual
Page 39
39
Drive Modbus I/O Control Input Instance 100 (64 Hex)
This I/O instance allows all drive parameters and monitors to be read/set. This instance is for Yaskawa drives only, and is not
interchangeable with other DeviceNet drives, Assembly Object Class (04 Hex) Attribute (03 Hex). Both input/output use 5
bytes each. Refer to the Appendix A for a list of Modbus Registers.
Table 17: Drive Modbus I/O Control Instance 100 (64 Hex) (INPUT ASSEMBLY)
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Function Code
1
Register Number (Upper Byte)
2
Register Number (Lower Byte)
3
Register Data (Upper Byte)
4
Register Data (Lower Byte)
Data
Name
Description
Byte 0
Function Code
Modbus (reference message) function code is set.
03 Hex: Read
10 Hex: Write
00 Hex: Undetermined
Byte 1, 2
Register Number (Upper and Lower Byte)
A drive Modbus register No. is set.
Byte 3, 4
Register Data (Upper and Lower Byte)
The write data at Modbus write command is set.