Drive Modbus I/O Control Input Instance 100 (64 Hex)

This I/O instance allows all drive parameters and monitors to be read/set. This instance is for Yaskawa drives only, and is not

interchangeable with other DeviceNet drives, Assembly Object Class (04 Hex) Attribute (03 Hex). Both input/output use 5

bytes each. Refer to the Appendix A for a list of Modbus Registers.

Table 17: Drive Modbus I/O Control Instance 100 (64 Hex) (INPUT ASSEMBLY)

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Function Code

1

Register Number (Upper Byte)

2

Register Number (Lower Byte)

3

Register Data (Upper Byte)

4

Register Data (Lower Byte)

Data

Name

Description

Byte 0

Function Code

Modbus (reference message) function code is set.
03 Hex: Read
10 Hex: Write
00 Hex: Undetermined

Byte 1, 2

Register Number (Upper and Lower Byte)

A drive Modbus register No. is set.

Byte 3, 4

Register Data (Upper and Lower Byte)

The write data at Modbus write command is set.