DeviceNet Fault Diagnostics
Drive Faults

Table 44: DeviceNet Fault Codes

DeviceNet

Fault Code No. (Hex)

Operator Fault

Display

Content

0000
2120
2130

-

GH

SC

Drive normal

Ground fault

Load short

2200

OL2

Drive overload

2220

OL1

Motor overload

2221

OL3

Overtorque 1

2222

OL4

Overtorque 2

2300

OC

Overcurrent

3130

PF

Main circuit voltage fault

LF

Output phase missing

3210

OV

Main circuit overvoltage

3220

UV1

Main circuit low voltage

3222

UV3

Surge protection circuit fault

4200

OH

Heat sink fin overheat

5110

UV2

Control power fault

5120

PUF

Fuse open

5300

OPR

Operator not connected

6320

ERR

EEPROM write failure

7110

RR

Braking transistor fault

7112

RH

Braking resistor overheat

7301

PGO

PG wire broken detection

7310

OS

Excessive speed

DEV

Speed deviation excessive

7500

BUS

Option communication error

9000

EF3

External fault (Input terminal S3)

EF4

External fault (Input terminal S4)

EF5

External fault (Input terminal S5)

EF6

External fault (Input terminal S6)

EF7

External fault (Input terminal S7)

EF8

External fault (Input terminal S8)

EF0

Option external fault

Advertising