Extended speed control input instance 21 (15 hex) – Yaskawa DeviceNet Option Card CM059 User Manual

Page 37

Advertising
background image

37

Extended Speed Control Input Instance 21 (15 Hex)

This function is the basic I/O instance of Assembly Object Class (04 Hex) Attribute (03 Hex), which is defined by the
DeviceNet AC Drive Profile. This is the Factory Default. Both I/O Assemblies use 4 bytes.

Table 15: Drive Extended Speed Control Instance21 (15 Hex) (INPUT ASSEMBLY)

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

NetRef

NetCtrl

Fault Reset

Rev Run

Fwd Run

1

2

Speed Reference (Lower Byte)

3

Speed Reference (Upper Byte)

Data

Name

Description

Byte 0, Bit 0

Fwd Run

The drive runs forward.

0: Stop
1: Fwd run

Byte 0, Bit 1

Rev Run

The drive runs reverse.

0: Stop
1: Rev. run

Byte 0, Bit 2

Fault Reset

The drive resets at fault detection status.

0: Fault reset off
1: Fault reset

Byte 0, Bit 5

NetCtrl

Run command rights are set.
0: Run command input procedures are set by set run command selection (b1-02)
1: Run command (Byte 0 – Bit 0, 1) through DeviceNet enabled.

Byte 0, Bit 6

NetRef

Frequency reference rights are set.
0: Frequency reference input procedures set by frequency reference selection (b1-01)
1: Frequency reference (Byte 2, 3) through DeviceNet enabled.

Byte 2, 3

Speed Reference

The drive speed reference is set.
This function is the same as the Speed Reference in the Basic Speed Control Input
Instance 20 (14 Hex) section.