Yaskawa DeviceNet Option Card CM059 User Manual

Page 44

Advertising
background image

44

*1 Drive products may provide additional inputs and outputs that are not supported through DeviceNet. For example, G7 has 5

digital outputs; however, only 3 digital outputs are supported through DeviceNet.

Table 21: Standard Drive Control Instance 151 (97 Hex) (OUTPUT ASSEMBLY)

*1

(Cont.)

Byte 1, Bit 1

During UV

The drive low voltage error (UV) detection status is displayed.
0: Normal
1: During UV detection

Byte 1, Bit 2

Local/Remote

The drive run command input selection status is displayed.
0: Run command input is enabled other than the DeviceNet.
1: Run command input is enabled from DeviceNet.

Byte 1, Bit 3

Terminal M1-M2

The drive multi-function output terminal M1-M2 output status is
displayed.
0: Terminal M1-M2 OFF
1: Terminal M1-M2 ON

Byte 1, Bit 4

Terminal M3-M4

The drive multi-function output terminal M3-M4 output status is
displayed.
0: Terminal M3-M4 OFF
1: Terminal M3-M4 ON

Byte 1, Bit 5

Terminal M5-M6

The drive multi-function output terminal M5-M6 output status is
displayed.
0: Terminal M5-M6 OFF
1: Terminal M5-M6 ON

Byte 1, Bit 6

Not Used

-

Byte 1, Bit 7

During Zero Servo

Displays the zero servo complete status of drive.
0: Zero servo not complete or not input.
1: Zero servo complete.

Byte 2, 3

Speed Monitor

The drive speed is displayed.
This function is the same as the Speed Monitor in Basic Speed
Control Output Instance 70 (46 Hex) section.

Byte 4, 5

Torque Reference

Displays the torque reference of the drive.
The unit is fixed at 0.1%.

Byte 6, 7

Output Current Monitor

The drive output current is displayed. The unit (0.1A) is fixed.
There is no effect on the current scale

setting.

Advertising