Monitor Data Transfer

In unbalanced mode the polling procedure is initiated from the master unit
through Class 1 and Class 2 requests. In general, ASDUs containing the causes
of transmission periodic/cyclic are assigned to be transmitted with class 2
requests and all time tagged or spontaneously transmitted ASDUs are assigned
to be transmitted through class 1 requests. Other ASDUs with other causes of
transmission of low priority such as background scan may also be assigned to
class 2 requests.

Typically, you should properly configure the group code for each monitor point to
define how the master will poll for the point. The group codes are defined as
follows:

The Group parameter is defined as follows:

Group Code

Description

0x00000001

Interrogated by general interrogation (station or global)

0x00000002

Interrogated by group 1 interrogation

0x00000004

Interrogated by group 2 interrogation

0x00000008

Interrogated by group 3 interrogation

0x00000010

Interrogated by group 4 interrogation

0x00000020

Interrogated by group 5 interrogation

0x00000040

Interrogated by group 6 interrogation

0x00000080

Interrogated by group 7 interrogation

0x00000100

Interrogated by group 8 interrogation

0x00000200

Interrogated by group 9 interrogation

0x00000400

Interrogated by group 10 interrogation

0x00000800

Interrogated by group 11 interrogation

0x00001000

Interrogated by group 12 interrogation

0x00002000

Interrogated by group 13 interrogation

0x00004000

Interrogated by group 14 interrogation

0x00008000

Interrogated by group 15 interrogation

0x00010000

Interrogated by group 16 interrogation

0x00020000

Interrogated by general counter request

0x00040000

Interrogated by group 1 counter request

0x00080000

Interrogated by group 2 counter request

0x00100000

Interrogated by group 3 counter request

0x00200000

Interrogated by group 4 counter request

0x40000000

Disable event scanning of this point

0x80000000

Periodic/cyclic data returned from unit

The module will periodically send all points configured for periodic/cyclic poll
(0x80000000) at every x milliseconds, where x is configured with the following
parameter:

Cyclic data transmission: 20000 #Numb of milliseconds between cyclic

#updates