M_me_na, M_me_nb – ProSoft Technology MVI69-101S User Manual

Page 114

Advertising
background image

MVI69-101S ♦ CompactLogix or MicroLogix Platform

Reference

IEC 60870-5-101 Slave Communication Module

Page 114 of 149

ProSoft Technology, Inc.

March 16, 2009

# ------- ---------- -------- -------- ---------

START

400 100 80000000 100 0# P1 suction pressure

401 101 00000200 100 0# P1 discharge pressure

402 102 00000400 100 0# P2 suction pressure

403 103 00000800 100 0# P2 discharge pressure

404 104 00001000 100 0# Station discharge

# pressure

END

[M_ME_NB_1]

#

# Default

# Point # DB Address Group(s) Deadband IV DB Bit

# ------- ---------- -------- -------- ---------

START

500 105 80000000 100 0

501 106 00000200 100 0

502 102 00000400 1 0

503 103 00000800 1 0

504 104 00001000 1 0

END

And if the parameter points are configured as follows:

M_ME_NA Parameter Offset : 2000 #M_ME_NA IOA offset for parameter data

M_ME_NB Parameter Offset : 2000 #M_ME_NB IOA offset for parameter data

It would imply that the parameter points would be configured as follows:

M_ME_NA

Monitored Measured Normalized Point

Associated Parameter Point

400 2400

401 2401

402 2402

403 2403

404 2404

M_ME_NB

Monitored Measured Normalized Point

Associated Parameter Point

500 2500

501 2501

502 2502

503 2503

504 2504