Normal data transfer, Read block – ProSoft Technology MVI69-101S User Manual

Page 78

Advertising
background image

MVI69-101S ♦ CompactLogix or MicroLogix Platform

Reference

IEC 60870-5-101 Slave Communication Module

Page 78 of 149

ProSoft Technology, Inc.

March 16, 2009

Data contained in this database is paged through the input and output images by
coordination of the CompactLogix or MicroLogix ladder logic and the MVI69-
101S module's program. The read and write block identification codes in each
data block determine the function to be performed or the content of the data
block. The module uses the following block numbers:

Block Range

Descriptions

0, -1

Status Block

1 to 67

Read or Write Data

1000 to 1067

Request Output Data from Processor

9958

Event Messages from CLX

9970

Set PLC time using module's time

9971

Set module's time using CLX time

9998

Warm-boot control block

9999

Cold-boot control block

Each image has a defined structure depending on the data content and the
function of the data transfer.

5.2.2 Normal Data Transfer

Normal data transfer includes the paging of the user data found in the module's
internal database in registers 0 to 4999 and the status data. These data are
transferred through read (input image) and write (output image) blocks. Refer to
the Module Configuration and Ladder Logic sections for a description of the
data objects used with the blocks and the ladder logic required. The structure
and function of each block is discussed in the following topics.

Read Block

These blocks of data transfer information from the module to the CompactLogix
or MicroLogix processor. The structure of the input image used to transfer this
data is shown below:

Offset Description

Length

0

Read Block ID

1

1

Write Block ID

1

2 to (n+1)

Read Data

n

where

n = 60, 120, or 240 depending on the Block Transfer Size parameter (refer to the
configuration file).

The Read Block ID is an index value used to determine the location of where the
data will be placed in the CompactLogix or MicroLogix processor controller tag
array of module read data. The number of data words per transfer depends on
the configured Block Transfer Size parameter in the configuration file (possible
values are 60, 120, or 240).