Monitor points addressing, M_sp_na and m_dp_na – ProSoft Technology MVI69-101S User Manual

Page 105

Advertising
background image

Reference MVI69-101S

♦ CompactLogix or MicroLogix Platform

IEC 60870-5-101 Slave Communication Module

ProSoft Technology, Inc.

Page 105 of 149

March 16, 2009

Mode D

To select the Mode D. configure the Freeze Start Type parameter as "N". For this
mode the master would periodically send Counter Interrogation Commands to
perform the freeze operation. After the values are frozen the module will return
the counter points as events. The counter points must be properly configured for
counter interrogation groups for Mode D operation.

The following illustration shows a typical communication example when the Mode
D is selected during unbalanced mode operation:

Monitor Points Addressing

As discussed before, the monitor points must be configured in a database area in
the MVI69-101S module.

The monitor data types are described in the following table.

Data Type

Data Size

Addressing Type

M_SP_NA 1

bit

Bit

M_DP_NA 2

bits

Bit

M_ST_NA 1

byte

Byte

M_ME_NA 1

word

Word

M_ME_NB 1

word

Word

M_ME_NC 2

word

Double-Word

M_IT_NA 2

word

Double-Word

M_SP_NA and M_DP_NA

The monitored single-point (1 bit) and monitored double-point (2 bits) types both
occupy bit-addressing. For example, if you configured the following points:

# Point # DB Address Group(s) IV DB Bit

# ------- ---------- -------- -------------

START

100 1600 80000000 0

101 1601 00000200 0

102 1602 00000400 0

END