Reference MVI69-101S

♦ CompactLogix or MicroLogix Platform

IEC 60870-5-101 Slave Communication Module

ProSoft Technology, Inc.

Page 97 of 149

March 16, 2009

The points that are typically transferred from the slave to the master are also
known as Monitor Points (or Monitor Information Objects). The points that are
typically transferred from the master to the slave are also known as Control
Points (or Command Information Objects).

For the MVI69-101S, the control and monitor points would be transferred as
follows:

You must make sure that all points are configured in the correct location in the
MVI69-101S module database in order to be properly updated from/to the
processor.

5.3.4 Using

Monitor

Points

The following monitor points are supported by the MVI69-101S module:

Symbol Description

Data Size in
Database

Addressing Type

M-SP-NA

Monitored Single-Points

1 bit

Bit

M-DP-NA

Monitored Dual-Points

2 bits

Bit

M-ST-NA

Monitored Step-Points

1 byte

Byte