MVI69-101S ♦ CompactLogix or MicroLogix Platform

Diagnostics and Troubleshooting

IEC 60870-5-101 Slave Communication Module

Page 70 of 149

ProSoft Technology, Inc.

March 16, 2009

To begin the display of the communications data, you will then want to press 'B'
to tell the module to start printing the communications traffic out on the debug
port of the module. After you have pressed 'B', you should see something like the
following:

The <R+> means that the module is transitioning the communications line to a
transmit state.

All characters shown in <> brackets are characters being sent out by the module.

The <R-> shows when the module is done transmitting data, and is now ready to
receive information back.

And finally, all characters shown in the [ ] brackets is information being received
from another device by the module.

After taking a minute or two of traffic capture, you will now want to stop the "Data
Analyzer". To do so, press the 'S' key, and you will then see the scrolling of the
data stop.

When you have captured the data you want to save, open the Transfer menu and
choose Capture Text. On the secondary menu, choose Stop.

You have now captured, and saved the file to your PC. This file can now be used
in analyzing the communications traffic on the line, and assist in determining
communication errors.