ProSoft Technology MVI69-101S User Manual

Page 79

Advertising
background image

Reference MVI69-101S

♦ CompactLogix or MicroLogix Platform

IEC 60870-5-101 Slave Communication Module

ProSoft Technology, Inc.

Page 79 of 149

March 16, 2009

The Write Block ID associated with the block requests data from the
CompactLogix or MicroLogix processor. Under normal, program operation, the
module sequentially sends read blocks and requests write blocks. For example, if
three read and two write blocks are used with the application, the sequence will
be as follows:

R1W1

R2W2

R3W1

R1W2

R2W1

R3W2

R1W1

This sequence will continue until interrupted by other write block numbers sent by
the controller or by a command request from a node on the 101S network or
operator control through the module's Configuration/Debug port.

The following example shows a typical backplane communication application.

Assume that the backplane parameters are configured as follows:

Read Register Start: 0

Read Register Count: 480

Write Register Start: 480

Write Register Count: 480

The backplane communication would be configured as follows:

Database address 0 to 479 will be continuously transferred from the module to
the processor. Database address 480 to 959 will continuously be transferred
from the processor to the module.

The Block Transfer Size parameter basically configures how the Read Data and
Write Data areas are broken down into data blocks (60, 120, or 240).

Advertising