2.3.5 Common address of ASDU

Common address of ASDU : 1 #Range 0 to 65535

This parameter specifies the common address of the ASDU (section address) for
access to data in the module. There is only one value entered for access to all
data in the module.

2.3.6 Common address of ASDU Len

1 or 2

This parameter specifies the number of octets used for the common address of
ASDU. This parameter must be set the same for all devices on the network.

2.3.7 Inform. Object address Len

1, 2 or 3

This parameter sets the number of octets used to specify the address for an
information object in each sector for this session.

2.3.8 Select/Operate

Timeout

Select/Operate Timeout : 2000 #Milliseconds before select timeout

This parameter sets the number of milliseconds after a select command is
received in which to wait for a valid execute command. If the parameter is set to
0, the feature will be disabled.

2.3.9 Cyclic Data Transmission

Cyclic data transmission : 60000 #Numb of milliseconds between cyclic

#updates

This parameter defines the number of milliseconds between cyclic updates. If the
parameter is set to 0, cyclic data reporting will be disabled.

2.3.10 Use ACTTERM with Setpoint

Use ACCTERM with setpoint : 1 #1=Yes, 0=No aCTCON is last response

#to cmd

This parameter determines if an ACCTERM will be sent. If the parameter is set to
Y, then setpoint commands will issue an ACCTERM when the command is
complete. If the parameter is set to N, aCTCON is the last response to a setpoint
command.