Example I - Freeze Start Type

If the module powers up with the following date and time clock:

03/25/2004 18:07:42

If you configure the Interval For Freeze parameter as follows:

Interval For Freeze : 15 #Number of seconds after start

#type (0 to 65535)

The module would send the counter messages every 15 seconds. The module
would start sending the messages depending on the Freeze Start Type
parameter as follows:

Freeze Start Type

Time to Start Sending Messages

D 03/26/2004

00:00:00

H 03/25/2004

19:00:00

M 03/25/2004

18:08:00

Example II - Freeze Start Type

If the module should send the counter points on the hourly turn around time and
also 45 minutes later, the Mode A parameters should be configured as follows:

Freeze Start Type : H #D=Day, H=Hour, M=Minute, N=Not

#used

Interval For Freeze : 2700 #Number of seconds after start

#type (0 to 65535)

So the module would send events as follows (Hours:Minutes:Seconds):

17:00:00

17:45:00

18:00:00

18:45:00

19:00:00

19:45:00

The following illustration shows a typical communication example when the Mode
A is selected during unbalanced mode operation: