Reference MVI69-101S

♦ CompactLogix or MicroLogix Platform

IEC 60870-5-101 Slave Communication Module

ProSoft Technology, Inc.

Page 133 of 149

March 16, 2009

Application Layer

Transmission mode for application data

Mode 1 (Least significant octet first), as defined in clause 4.10 of IEC 60870-5-4,
is used exclusively in this companion standard.

Common address of ASDU

(System-specific parameter)

⌧ One octet ⌧ Two octets

Information object address

(System-specific parameter)

One octet

⌧ structured

⌧ Two octets ⌧ unstructured

⌧ Three octets

Cause of transmission

(System-specific parameter)

⌧ One octet S Two octets (with originator address)

Selection of standard ASDUs

Process information in monitor direction

(Station-specific parameter)

<1>

:= Single-point information

M_SP_NA_1

<2>

:= Single-point information with time tag

M_SP_TA_1

<3>

:= Double-point information

M_DP_NA_1

<4>

:= Double-point information with time tag

M_DP_TA_1

<5>

:= Step position information

M_ST_NA_1

<6>

:= Step position information with time tag

M_ST_TA_1

<7>

:= Bitstring of 32 bit

M_BO_NA_1

<8>

:= Bitstring of 32 bit with time tag

M_BO_TA_1

<9>

:= Measured value, normalized value

M_ME_NA_1

<10> := Measured value, normalized value with time tag M_ME_TA_1

<11> := Measured value, scaled value

M_ME_NB_1

<12> := Measured value, scaled value with time tag

M_ME_TB_1