Configuring the MVI69-101S Module

MVI69-101S ♦ CompactLogix or MicroLogix Platform

IEC 60870-5-101 Slave Communication Module

ProSoft Technology, Inc.

Page 43 of 149

March 16, 2009

The database address should be located in a database area that is being
constantly moved from the MVI69-101S to the CompactLogix or MicroLogix
processor. You should configure the DB address parameter in an area that is on
a Backplane Command Function 2.

2.17 [C_SE_NC_1]

This section defines the short-float setpoint database for the slave emulated. This
information is sourced from the remote master and is transferred to the database.
Each point occupies a double-word position in the database. If the Require
Select parameter is not set to zero, a select command must be received before
an execute command will be processed.

This section takes the following parameters:

Point

#

DB

address

Monitor Point #
Monitor

DB

addr

Require

Select

Each point is two words and the DB address value corresponds to the double-
word offset in the database.

The database address should be located in a database area that is being
constantly moved from the MVI69-101S to the CompactLogix or MicroLogix
processor. You should configure the DB address parameter in an area that is on
a Backplane Command Function 2.

Note:
Monitor Point # and Monitor DB Addr
You can also associate a monitor point with each command point. Therefore, every time the
module responds to a command, it will include the monitor point with the information object
address given by the Monitor Point # parameter. Its value will be copied from the database address
location given by the Monitor DB Address parameter.
Require Select
This parameter specifies if the point requires a "select" before an "Operation" command.

2.18 Download

the

Project to the Module

In order for the module to use the settings you configured, you must download
(copy) the updated Project file from your PC to the module.

To Download the Project File

1 In the tree view in ProSoft Configuration Builder, click once to select the

MVI69-101S module.