You can check the current date and time using the debug menu. Press [E] at the
main menu to view the Module Status Data screen:

You can also configure the module to copy the date and time information to the
module database with the following parameter:

Time DB Offset : 2000 #DB location of IEC time (-1=ignore)

As the module sends events to the master (serial modules) or client (ethernet
modules), it also sends a Clock Synchronization response (spontaneous COT)
every hour for the transmission of the clock time to the master (serial modules) or
client (ethernet modules).

Event Priority

Event Priority permits ASDUs that generate events to be placed in priority
queues that are set by the user. The configuration file contains the following
parameters to support this feature:

[IEC-870-5-101 Port 0]

Set Priority Queues : 1 #Set user defined priority queues 1=Yes,

#0=No

M_SP_NA Priority : 1 #Unique index for this data type in queue

#(0-5)

M_DP_NA Priority : 0 #Unique index for this data type in queue

#(0-5)

M_ST_NA Priority : 5 #Unique index for this data type in queue

#(0-5)

M_ME_NA Priority : 4 #Unique index for this data type in queue

#(0-5)

M_ME_NB Priority : 3 #Unique index for this data type in queue

#(0-5)

M_ME_NC Priority : 2 #Unique index for this data type in queue

#(0-5)

M_IT_NA Priority : 6 #Unique index for this data type in queue

#(0-5)