Mvi69101s_control, Mvi69101s_eventblock, Mvi69101s_event – ProSoft Technology MVI69-101S User Manual

Page 47: Mvi69101s_clock

Advertising
background image

Ladder Logic

MVI69-101S ♦ CompactLogix or MicroLogix Platform

IEC 60870-5-101 Slave Communication Module

ProSoft Technology, Inc.

Page 47 of 149

March 16, 2009

3.1.2 MVI69101S_CONTROL

The CONTROL tag contains special tags for special tasks to be requested to the
module.

Name Data

Type

Description

Event

MVI69101S_EventBlock

Block 9958: Event message

SetTime MVI69101S_Clock

Block 9971: Writes the clock data to
the module

GetTime MVI69101S_Clock

Block 9970: Reads the clock data from
the module

MVI69101S_EventBlock

Name Data

Type

Description

Activate BOOL

Set this bit to 1 to activate event block
9958 to send events to the module

EventCount INT

Number of events to be sent at this
block (between 1 and 3)

Event MVI69101S_Event[3]

MVI69101S_Event

The Event tag describes the format of each event to be transferred from the
processor to the module.

Name Data

Type

Description

DBIndex

INT

Index of the point in configuration file

ASDU INT

1=SP, 3=DP, 5=STEP,9=NORM,
11=SCALED, 15=INTEGRATED

Qualifier INT

Qualifier

Code

Year

INT

Year of timestamp

Month

INT

Month of timestamp

Day INT

Day

of

timestamp

Hour

INT

Hour of timestamp

Minute

INT

Minute of timestamp

Seconds_Milliseconds INT

For example, a value of 15742 means
15secs and 742 milliseconds

Data INT[6]

Data associated to event: data size will
depend on point type - check
documentation

MVI69101S_Clock

The Clock tag contains the format to read and write the module's date and time
information.

Name Data

Type

Description

Activate BOOL

Year INT

Month INT

Advertising