3.1.4 Block Control Data - MVI69101S_UTIL

This data object stores the variables required for the data transfer between the
processor and the MVI69-101S module. The structure of the object is shown in
the following table.

Name Data

Type

Description

Warmboot

BOOL

Requests warmboot of the module

ColdBoot

BOOL

Requests coldboot of the module

BPLastRead

INT

Index of last read

BPLastWrite

INT

Index of last write

BlockIndex

INT

Computed block offset for data table

BootTimer TIMER

Used to clear output block ID after
power up

LoopIndex

INT

Used as index during Loops

BlockTransferSize INT

Must match the configuration
parameter Block Transfer (60, 120,
240). This value must be set in ladder
by the user

3.2

Adding the Module to an Existing CompactLogix Project

Important: The MVI69-101S module has a power supply distance rating of 2 (L43 and L45
installations on first 2 slots of 1769 bus)

If you are installing and configuring the module with a CompactLogix processor,
follow these steps. If you are using a MicroLogix processor, refer to the next
section.