MVI69-101S ♦ CompactLogix or MicroLogix Platform

Reference

IEC 60870-5-101 Slave Communication Module

Page 82 of 149

ProSoft Technology, Inc.

March 16, 2009

These areas are defined by the user when the configuration file is being edited.
The following parameters define the Read and Write data areas:

Read Register Start = 0

Read Register Count = 120

Write Register Start = 200

Write Register Count = 120

Each area is broken down into blocks of 60 words. Therefore, the Read Register
Count and Write Register Count parameters should be multiples of 60.

The Read Data Area will be transferred from the module to the CompactLogix or
MicroLogix processor. The Write Data Area will be transferred from the
CompactLogix or MicroLogix processor to the module.

The following example shows the resulting data flow:

5.2.3 Status

Block

The module periodically sends blocks 0 and -1 containing status information, as
described in the following table.

Offset Description

Length

0

Block Read ID

1

1

Block Write ID

1

2

Program Scan Counter

2

4 Product

Code

2

6 Product

Version

2

8 Operating

System

2

10 Run

Number

2

11

Backplane Read Count

1